E-MAX Sequential Event Recorder Specifications

Input Points 16 isolated or 32 non-isolated per card • 4 cards per input chassis
1024 points maximum per recorder.
Cable Specifications  

Type

Impedance

Capacitance

Velocity of propagation

Shielding

Connectors

Signal attenuation

RG-59

75 W

16.5 pF/foot or 54.1 pF/meter

84%

Foil and Copper braid

Waterproof F-type

<10 dB/100 feet for cable and connectors

Time Accuracy

Power Input

Surge Withstand Capability

1 Minute/year

90 to 160 Vdc 120 Vrms

ANSI/IEEE C37.90-1989
Input Points 100 percent tested for Common and Transverse Mode

Autotest Capability Time-based Self-Test Manual Point by Point Inspection capability
All Points Test
Reporting Capability Periodic or on Demand / Local or Remote Selection
Event Summary • Period Activity Summary • Historical Summary
Period Capability (1 minute to 1 year)
Alarms
1. System Operation
2. System Failure
3. DC Power
4. Loss of Time Sync.
5. Memory 75% Full
Panel LED indication with relay contact output for conditions below.
Record capture - Resets after data has been stored on the hard disk.
Deadman timer, system power supply failure or System OFF LINE.
Loss of system DC input power.
No primary time synchronization.
Data Record storage area more than 75% full.

Communications Capability

 

Auto Reporting • Responding to Polling • Multiple Station Reporting
Fax Report Output (optional)
Ethernet, Internet

Add-on Capability Modem Available — 56 kbps V. 90

Operating Temperature

Storage Temperature

Humidity

Shock and Vibration

-20° to +60° C

-40° to +70° C

0 to 95% R.H. maximum non-condensing

Consult factory for seismic qualification data

Configuration

Burn-in Test

19 inch rack mountable.

100 hour minimum