Home
Products
Software
Contact E-MAX
Visit Us
Site Map
    BVR Product Page


BVR - Battery Voltage Relay Specifications and Order Information
Part No.

Type

Input Voltage
Operate
Current
(dc amps)
999C125
Battery Voltage Relay
125 V
Over & Under Voltage
999C127
Battery Voltage Relay
48 V
Over & Under Voltage
999C128
Battery Voltage Relay
24 V
Over & Under Voltage
999C130
Battery Undervoltage Relay
125 V
Undervoltage Only
999C132
Battery Undervoltage Relay
48 V
Undervoltage Only
999C133
Battery Undervoltage Relay
24 V
Undervoltage Only
999C135
Battery Undervoltage Relay
250 V
Undervoltage Only
999C140
Battery Undervoltage Relay
125 V
Dual Set Point Undervoltage Only
999C141
Battery Undervoltage Relay
48 V
Dual Set Point Undervoltage Only
Setting Ranges 70 to 140% of nominal battery voltage
Accuracy Setting ±0.5 Volts over entire range of voltage and environments
Outputs UV N.C. Contacts — dropout for undervoltage
OV N.O. Contacts — close on overvoltage
Contact Rating Resistive Inductive
125 Vac 5 A 2.5 A
30 Vdc 3 A 0.6 A
expected life—5 x 105 operations at above ratings
Operate Time 2 seconds minimum
5 seconds nominal
Noise Immunity IEEE/ANSI Standard C 37.90a -1989 compliance
Case Dimensions 6.0 x 3.375 x 4.06 inches
Case Material Anodized Aluminum
Weight 1.0 - 1.5 lbs
Temperature Range
Operating 0 - 55 C
Storage -54 to 71 C

Setting

Single turn Locking Potentiometer
Midpoints Setting by internal potentiometer

Humidity

0 to 95% R.H. non-condensing

Vibration

0 to 2.5 g., Up to 25 Hz

E-MAX Instruments, Incorporated
13 Inverness Way South Englewood, Colorado 80112 Tel: 303.799.6640
© E-MAX Instruments, Incorporated 1996-2005 All Rights Reserved