MON-1 - Specifications and Order Information
Type Operating Sequence Input Power
MON -1
MON -1
MON -1
MON -1
MON -1
MON -1
Sequence 11
Sequence 11
Sequence 11
Sequence 12
Sequence 12
Sequence 12
24 Vdc
48 Vdc
125 Vdc
24 Vdc
48 Vdc
125 Vdc

 

Number of Points

 

10

Input Connections
Barrier Strip #12 wire maximum
Two terminations per point
All points commoned to one side of power supply
(positive common standard)
Input Contact Rating 25mA maximum
Input Contact Type N.O. or N.C. Slide Switch Selected

Operating Sequence — Sequence 11
Point Latching — Resettable Retransmit

Initiating
Contact
Lamp
Retransmit
Relay
Normal
Open
Off
Open
Alarm
Closed
On
Closed
Clear
Open
On
Closed
Reset
Open
Off
Open

Operating Sequence — Sequence 12
Point Latching — Resettable Retransmit

Initiating
Contact
Lamp
Retransmit
Relay
Normal
Open
Off
Open
Alarm
Closed
On
Closed
Clear
Open
On
Open
Reset
Open
Off
Open
Outputs  
Visual Indication High Brightness, 50 MCD, Red LED’s (plug-in replaceable)
Retransmitting Relays 2
Major / Minor Alarms Strap Selected
Contact Ratings 28 V 5A
125 V 0.5 Resistive
Cut -Out Switches One per Point
Noise Rejection SWC Test ANSI C37.90a-1974
Isolation All Field Contacts common
1500 V rms 60 Hz to ground
Dimensions 5.5 H x 9.5 W x 9.25 D
Environmental
Temperature: Operating -20° to 50° C
Storage -55
° to 70° C
E-MAX Instruments, Incorporated
13 Inverness Way South Englewood, Colorado 80112 Tel: 303.799.6640
© E-MAX Instruments, Incorporated 1996-2003 All Rights Reserved

 